About the KILock
The KILock (ZITKIL) is the Zennio KNX interface to the electronic lock of a hotel room[1]. It talks to the lock both ways over 2.4 GHz radio[1][2]: to Vingcard over Zigbee and, from application program 2.0, to Onity over Bluetooth Low Energy[2]. With Onity it also controls the lock from KNX: Do Not Disturb and the room status on the lock LEDs, never the bolt[2]. One interface serves one lock[1]; via the KILock Server, lock events also reach the lock system server[2].
It takes 1 DIN unit, runs on bus power (9.5 mA at 29 V, 12.5 mA at 24 V worst case), operates from 0 to +55 °C and supports KNX Data Secure[1]. The radio range of up to 35 m depends on conditions, device orientation and surrounding materials[1].
A lost link shows at once: the PAIR LED of a paired interface blinks green[1], and ETS can add a one-bit communication error alarm with selectable polarity[2]. The first heartbeat after a download or bus failure is delayed by up to 255 seconds, and optional Device Recovery objects send 0 and 1 at every start[2]. A KNX Secure factory reset needs safe mode first: keep the programming button pressed while connecting the device to the bus, then press it for 10 seconds until the LED changes[1].
Sources
Linked documents are in English.
- [1]KILock — Zennio, datasheet (PDF) ↩
- [2]KILock — user manual — Zennio, user manual (PDF) ↩
Technical Specifications
Documentation
Manufacturer documents are in English
Datasheets
Manuals
Interested in this product?
Contact us, the official ZENNIO distributor in Kazakhstan, for availability, equipment selection and technical support.
Phone and WhatsApp: +7 777 678 77 88