About the KLIC-DI v2

The KLIC-DI v2 is a Zennio gateway for Daikin SKY Air commercial units and VRV industrial systems, joined to the indoor unit's 2-wire line for two-way data[1]. The 67 × 90 × 36 mm DIN-rail module sits in the panel, on a line of up to 100 m to the unit, and draws 4.5 mA from the KNX bus[2]. ETS sets the unit type, VRV or Sky Air[1].

If the Daikin wired remote stays, decide before start-up who leads, the gateway or the remote: one is master, the other slave. On R-32 units a Madoka remote is mandatory as master, with the gateway as slave; after a role change the remote is restarted by cutting its power. In VRV without a BS box only one indoor unit switches the mode, and the rest choose only modes compatible with it: while it heats, they get heat and fan[1].

Setpoints span 16–32 °C, the fan has 2, 3 or 5 speeds as the unit allows, and a filter-cleaning flag can be reset from KNX[1]. Each of the two inputs serves a probe, a Zennio motion sensor or a push button, on cable runs up to 30 m[2]. For a VRV office or building we check the indoor units in the Zennio tool[3] and list the gateways and panels.

Works with

Sources

Linked documents are in English.

  1. [1]KLIC-DI v2 — user manual — Zennio, user manual (PDF) ↩
  2. [2]KLIC-DI v2 — Zennio, datasheet (PDF) ↩
  3. [3]Zennio compatibility tool (KLIC gateways) ↩
  4. [4]Flat AmbienT — Zennio, datasheet (PDF) ↩
  5. [5]Temperature Probe — Zennio, datasheet (PDF) ↩
  6. [6]EyeZen IN — Zennio, datasheet (PDF) ↩

Interested in this product?

Contact us, the official ZENNIO distributor in Kazakhstan, for availability, equipment selection and technical support.

Phone and WhatsApp: +7 777 678 77 88

We set statistics cookies only with your consent. Cookie policy